1. Definitions and
Scope
1.1. A Home
inspection is a non-invasive visual examination of a
residential dwelling, performed for a fee, which is
designed to identify observed material defects
within specific components of said dwelling.
Components may include any combination of
mechanical, structural, electrical, plumbing, or
other essential systems or portions of the home, as
identified and agreed to by the Client and
Inspector, prior to or during the inspection
process.
I. A home
inspection is intended to assist in evaluation of
the overall condition of the dwelling. The
inspection is based on observation of the visible
and apparent condition of the structure and its
components on the date of the inspection and not
the determination of future conditions.
II. A home
inspection will not reveal every problem that
exists or ever could exist, but only those
material defects observed on the day of the
inspection.
1.2. A Material
defect is a problem with a residential real property
or any portion of it that would have a significant
adverse impact on the value of the property or that
involves an unreasonable risk to people on the
property. The fact that a structural element, system
or subsystem is near, at or beyond the end of the
normal useful life of such a structural element,
system or subsystem is not by itself a material
defect.
1.3. An Inspection
report shall describe and identify in written format
the inspected systems, structures, and components of
the dwelling and shall identify material defects
observed. Inspection reports may contain
recommendations regarding conditions reported or
recommendations for correction, monitoring or
further evaluation by professionals.
|
2.
Standards of Practice
2.1.
Roof
I.
The inspector shall inspect from ground level or
eaves:
A.
The roof covering.
B. The gutters.
C. The downspouts.
D. The vents, flashings, skylights, chimney and
other roof penetrations.
E. The general structure of the roof from the
readily accessible panels, doors or stairs.
II.
The inspector is not required to:
A.
Walk on any roof surface.
B. Predict the service life expectancy.
C. Inspect underground downspout diverter
drainage pipes.
D. Remove snow, ice, debris or other conditions
that prohibit the observation of the roof
surfaces.
E. Inspect antennae, lightning arresters, or
similar attachments.
2.2.
Exterior
I.
The inspector shall inspect:
A.
The flashing and trim.
B. All exterior doors, decks, stoops, steps,
stairs, porches, railings, eaves, soffits,
fascias, grading, and walkways.
C. And report as in need of repair any spacings
between intermediate balusters, spindles, or
rails for steps, stairways, balconies, and
railings that permit the passage of an object
greater than four inches in diameter.
D. The vegetation, surface drainage and
retaining walls when these are likely to
adversely affect the building.
E. And describe the exterior wall covering.
II.
The inspector is not required to:
A.
Inspect or operate screens, storm windows,
shutters, awnings, fences, outbuildings, or
exterior accent lighting.
B. Inspect items, including window and door
flashings, which are not visible or readily
accessible from the ground.
C. Inspect geological, geotechnical, or
hydrological conditions.
D. Inspect recreational facilities.
E. Inspect seawalls, break-walls and docks.
F. Inspect erosion control and earth
stabilization measures.
G. Inspect for safety type glass.
H. Inspect underground utilities.
I. Inspect underground items.
J. Inspect wells or springs.
K. Inspect solar systems.
L. Inspect swimming pools or spas.
M. Inspect septic systems or cesspools.
N. Inspect playground equipment.
O. Inspect sprinkler systems.
P. Inspect drain fields or drywells.
Q. Determine the integrity of the thermal window
seals or damaged glass.
2.3.
Basement, Foundation & Crawlspace
I.
The inspector shall inspect:
A.
The basement.
B. The foundation
C. The crawlspace.
D. The visible structural components.
E. Any present conditions or indications of
active water penetration by probing a
representative sampling of structural components
where deterioration is believed to be present or
where clear indications of deterioration are
present.
F. And report any general indications of
foundation movement that are observed, such as
but not limited to sheetrock cracks, brick
cracks, out-of-square door frames or floor
slopes.
II.
The inspector is not required to:
A.
Enter any crawlspaces that are not readily
accessible or where entry could cause damage or
pose a hazard to the inspector in his or her
opinion.
B. Move stored items or debris.
C. Operate sump pumps with inaccessible floats.
D. Identify size, spacing, span, location or
adequacy of foundation bolting, bracing, joists
or support systems.
E. Provide any engineering or architectural
service.
F. Report on the adequacy of any structural
system or component.
2.4. Heating
I.
The inspector shall inspect:
A.
The heating system and describe the energy
source and heating method using normal operating
controls.
B. And report as in need of repair electric
furnaces which do not operate.
C. And report if inspector deemed the furnace
inaccessible.
II.
The inspector is not required to:
A.
Inspect or evaluate interiors of flues or
chimneys, fire chambers, the heat exchanger, the
humidifier or dehumidifier, the electronic air
filter, solar heating systems or fuel tanks.
B. Inspect underground fuel tanks.
C. Determine the uniformity, temperature, flow,
balance, distribution, size, capacity, BTU, or
supply adequacy of the heating system.
D. Light pilot flames.
E. Activate heating, heat pump systems, or other
heating systems when ambient temperatures or
other circumstances are not conducive to safe
operation or may damage the equipment.
F. Operate electronic thermostats.
G. Evaluate fuel quality.
2.5.
Cooling
I.
The inspector shall inspect:
A.
The central cooling equipment using normal
operating controls.
II.
The inspector is not required to:
A.
Determine the uniformity, temperature, flow,
balance, distribution, size, capacity, BTU, or
supply adequacy of the cooling system.
B. Inspect window units, through-wall units, or
electronic air filters.
C. Operate equipment or systems if exterior
temperature is below 60 degrees Fahrenheit or
when other circumstances are not conducive to
safe operation or may damage the equipment.
D. Inspect or determine thermostat calibration,
heat anticipation or automatic setbacks or
clocks.
E. Examine electrical current, coolant fluids or
gasses, or coolant leakage.
2.6.
Plumbing
I.
The inspector shall:
A.
Inspect the main water shut off valve.
B. Inspect the water heating equipment,
including combustion air, venting,
connections, energy sources, seismic bracing,
and verify the presence or absence of
temperature-pressure relief valves and/or
Watts 210 valves.
C. Flush toilets.
D. Run water in sinks, tubs, and showers.
E. Inspect the interior water supply including
all fixtures and faucets.
F. Inspect the drain, waste and vent systems,
including all fixtures.
G. Describe any visible fuel
storage systems.
H. Inspect the drainage sump pumps testing
sumps with accessible floats.
I. Inspect and describe the water supply,
drain, waste and main fuel shut-off valves, as
well as the location of the water main and
main fuel shut-off valves.
J. Inspect and determine if the water supply
is public or private.
K. Inspect and report as in need of repair
deficiencies in the water supply by viewing
the functional flow in two fixtures operated
simultaneously.
L. Inspect and report as in need of repair
deficiencies in installation and
identification of hot and cold faucets.
M. Inspect and report as in need of repair
mechanical drain-stops that are missing or do
not operate if installed in sinks, lavatories
and tubs.
N. Inspect and report as in need of repair
commodes that have cracks in the ceramic
material, are improperly mounted on the floor,
leak, or have tank components which do not
operate.
II.
The inspector is not required to:
A.
Light pilot flames.
B. Determine the size, temperature, age, life
expectancy or adequacy of the water heater.
C. Inspect interiors of flues or chimneys,
water softening or filtering systems, well
pumps or tanks, safety or shut-of valves,
floor drains or sprinkler systems.
D. Determine the exact flow rate, volume,
pressure, temperature, or adequacy of the
water supply.
E. Determine the water quality or potability
or the reliability of the water supply or
source.
F. Open closed plumbing access panels.
G. Inspect clothes washing machine
connections.
H. Operate any main, branch or fixture valve
except fixture faucets and hose faucets
attached to the building.
I. Test shower pans, tub and shower surrounds
or enclosures for leakage.
J. Evaluate the compliance with local or state
conservation or energy standards, or the
proper design or sizing of any water, waste or
venting components, fixtures or piping.
K. Determine the effectiveness of anti-siphon,
back-flow prevention or drain-stop devices.
L. Determine whether there are sufficient
clean-outs for effective cleaning of drains.
M. Evaluate gas, liquid propane or oil storage
tanks.
N. Excavate or otherwise uncover the private
sewage system or its components to determine
size, adequacy or efficiency.
O. Inspect water treatment systems or water
filters.
P. Inspect pressure pumps or bladder tanks.
Q.
Evaluate time to obtain hot water at
fixtures, or perform testing of any kind to
water heater elements.
R.
Evaluate or determine the adequacy of
combustion air.
S.
Test, operate, open or close Watts 210
valves and/or TPR valves.
T.
Examine ancillary systems or components,
such as, but not limited to, those relating
to solar water heating, hot water
circulation.
2.7.
Electrical
I.
The inspector shall inspect:
A.
The service line.
B. The meter box.
C. The main disconnect.
D. And determine the service
amperage.
E. Panels, breakers and fuses.
F. The grounding.
G. The bonding.
H. A representative sampling of switches,
receptacles, light fixtures, and test all GFCI
receptacles and GFCI circuit breakers observed
and deemed to be GFCI's during the inspection.
I.
And report the presence of solid conductor
aluminum branch circuit wiring if readily
visible.
J. And report on any GFCI-tested receptacles
in which power is not present, polarity is
incorrect, the receptacle is not
grounded, is not secured to the wall, the
cover is not in place, the ground fault
circuit interrupter devices are not properly
installed or do not operate properly, or
evidence of arcing or excessive heat is
present.
K. The service entrance conductors and the
condition of their sheathing.
L. The ground fault circuit interrupters with
a GFCI tester.
M. And describe the amperage rating of the
service.
N. And report the absence of smoke detectors.
O. Service entrance cables and report as in
need of repair deficiencies in the integrity
of the insulation, drip loop, or separation of
conductors at weatherheads and clearances.
II.
The inspector is not required to:
A.
Insert any tool, probe or device into the main
or sub-panels.
B. Operate electrical systems that are shut
down.
C. Remove panel covers or dead front covers if
not readily accessible.
D. Operate over current protection devices.
E. Operate non-accessible smoke detectors.
F. Measure or determine the amperage or voltage
of the main service if not visibly labeled.
G. Inspect the alarm system and components.
H. Inspect the ancillary wiring.
I. Activate any electrical systems or branch
circuits which are not energized.
J. Operate overload devices.
K. Inspect low voltage systems, electrical
de-icing tapes, swimming pool wiring or any
time-controlled devices.
L. Verify the continuity of the connected
service ground.
M. Inspect private or emergency electrical
supply sources, including but not limited to
generators, windmills, photovoltaic solar
collectors, or battery or electrical storage
facility.
N. Inspect spark or lightning arrestors.
O. Conduct drop voltage calculations.
P. Determine the accuracy of breaker labeling.
2.8.
Fireplace
I.
The inspector shall inspect:
A.
The fireplace, and open and close the damper
door if readily accessible and operable.
B. Hearth extensions and other permanently
installed components.
C. And report as in need of repair deficiencies
in the lintel, hearth and material surrounding
the fireplace, including clearance from
combustible materials
II.
The inspector is not required to:
A.
Inspect the vent system.
B. Inspect the interior of the chimney or flue,
fire doors or screens, seals or mantels.
C. Determine the need for a chimney sweep.
D. Operate gas fireplace inserts.
E. Light pilot flames.
F. Determine the appropriateness of such
installation.
G. Inspect automatic fuel feed devices.
H. Inspect combustion make up devices.
I. Inspect heat distribution assists whether
gravity controlled or fan assisted.
J. Ignite or extinguish fires.
K. Determine draft characteristics.
L. Move fireplace inserts, stoves, or firebox
contents.
M. Determine adequacy of draft, perform a smoke
test or dismantle or remove any component.
2.9.
Attic, Ventilation & Insulation
I.
The inspector shall inspect:
A.
The insulation in unfinished spaces.
B. The ventilation of attic spaces.
C. Mechanical ventilation systems.
D. And report on the general absence or lack of
insulation.
II.
The inspector is not required to:
A.
Enter the attic or unfinished spaces that are
not readily accessible or where entry could
cause damage or pose a safety hazard to the
inspector in his or her opinion.
B. To move or touch insulation.
C. To move or touch vapor retarders.
D. Break or otherwise damage the surface finish
or weather seal on or around access panels and
covers.
E. Identify the composition or the exact R-value
of insulation material.
F. Activate thermostatically operated fans.
G. Determine the types of materials used in
insulation/wrapping of pipes, ducts, jackets,
boilers, and wiring.
2.10.
Doors, Windows & Interior
I.
The inspector shall:
A.
Open and close a representative number of doors
and windows.
B. Inspect the walls, ceilings, steps,
stairways, and railings.
C. Inspect garage doors and garage door openers
by operating first by remote (if available) and
then by the installed automatic door control.
D. And report as in need of repair any installed
electronic sensors that are not operable or not
installed at proper heights above the garage
door.
E. And report as in need of repair any door
locks or side ropes that have not been removed
or disabled when garage door opener is in use.
F. And report as in need of repair any windows
that are obviously fogged or display other
evidence of broken seals.
II.
The inspector is not required to:
A.
Inspect paint, wallpaper, window treatments or
finish treatments.
B. Inspect central vacuum systems.
C. Inspect safety glazing in locations subject
to human impact.
D. Inspect security components.
E. Evaluate the fastening of countertops,
cabinets, sink tops and fixtures, or firewall
compromises.
F. Move furniture, stored items, or any
coverings like carpets or rugs in order to
inspect the concealed floor structure.
G. Move drop ceiling tiles.
H. Inspect or move any household appliances.
I. Inspect or operate equipment housed in the
garage except as otherwise noted.
J. Verify or certify safe operation of any auto
reverse or related safety function of a garage
door.
K. Operate or evaluate security bar release and
opening mechanisms, whether interior or
exterior, including compliance with local,
state, or federal standards.
L. Operate any system, appliance or component
that requires the use of special keys, codes,
combinations, or devices.
M. Operate or evaluate self-cleaning oven cycles
or signal lights.
N. Determine leakage from microwave ovens.
O. Operate or examine any sauna, steam-jenny,
kiln, toaster, ice-maker, coffee-maker,
can-opener, bread-warmer, blender, instant hot
water dispenser, or other small, ancillary
devices.
P. Inspect elevators.
Q. Inspect remote controls.
R. Inspect appliances.
S. Inspect items not permanently installed.
T. Examine or operate any above-ground, movable,
freestanding, or otherwise non-permanently
installed pool/spa or self-contained equipment.
U. Come into contact with any pool or spa water
in order to determine the system structure or
components.
V. Determine the adequacy of spa jet water force
or bubble effect.
W. Determine the structural integrity or leakage
of a pool or spa.
3.
Limitations, Exceptions & Exclusions
3.1.
Limitations:
I.
An inspection is not technically exhaustive.
II. An inspection will not identify concealed or
latent defects.
III. An inspection will not deal with aesthetic
concerns or what could be deemed matters of taste,
cosmetic, etc.
IV. An inspection will not determine the
suitability of the property for any use.
V. An inspection does not determine the market
value of the property or its marketability.
VI. An inspection does not determine the
advisability or inadvisability of the purchase of
the inspected property.
VII. An inspection does not determine the life
expectancy of the property or any components or
systems therein.
VIII. An inspection does not include items not
permanently installed.
IX. These Standards of Practice apply only to
homes with four or fewer dwelling units.
3.2. Exclusions:
I.
The inspectors are not required to determine:
A.
Property boundary lines or encroachments.
B. The condition of any component or system that
is not readily accessible.
C. The service life expectancy of any component
or system.
D. The size, capacity, BTU, performance, or
efficiency of any component or system.
E. The cause or reason of any condition.
F. The cause for the need of repair or
replacement of any system or component.
G. Future conditions.
H. The compliance with codes or regulations.
I. The presence of evidence of rodents,
animals or insects.
J. The presence of mold, mildew or fungus.
K. The presence of air-borne hazards.
L. The presence of birds.
M. The presence of other flora or fauna.
N. The air quality.
O. The existence of asbestos.
P. The existence of environmental hazards.
Q. The existence of electro-magnetic fields.
R. The presence of hazardous materials
including, but not limited to, the presence of
lead in paint.
S. Any hazardous waste conditions.
T. Any manufacturer recalls or conformance with
manufacturer installation or any information
included in the consumer protection bulletin.
U. Operating costs of systems.
V. Replacement or repair cost estimates.
W. The acoustical properties of any systems.
X. Estimates of how much it will cost to run any
given system.
II.
The inspectors are not required to operate:
A.
Any system that is shut down.
B. Any system that does not function properly.
C. Or evaluate low voltage electrical systems
such as, but not limited to:
1. Phone lines.
2. Cable lines.
3. Antennae.
4. Lights.
5. Remote controls.
D. Any system that does not turn on with the use
of normal operating controls.
E. Any shut off valve.
F. Any electrical disconnect or over current
protection devices.
G. Any alarm systems.
H. Moisture meters, gas detectors or similar
equipment.
III.
The inspectors are not required to:
A.
Move any personal items or other obstructions,
such as, but not limited to:
1.
Throw rugs.
2. Furniture.
3. Floor or wall coverings.
4. Ceiling tiles
5. Window coverings.
6. Equipment.
7. Plants.
8. Ice.
9. Debris.
10. Snow.
11. Water.
12. Dirt.
13. Foliage.
14. Pets
B.
Dismantle, open, or uncover any system or
component.
C. Enter or access any area which may, in the
opinion of the inspector, to be unsafe or risk
personal safety.
D. Enter crawlspaces or other areas that are
unsafe or not readily accessible.
E. Inspect underground items such as, but not
limited to, underground storage tanks or other
indications of their presence, whether abandoned
or actively used.
F. Do anything which, in the inspector's
opinion, is likely to be unsafe or dangerous to
the inspector or others or damage property, such
as, but not limited to, walking on roof
surfaces, climbing ladders, entering attic
spaces or negotiating with dogs.
G. Inspect decorative items.
H. Inspect common elements or areas in
multi-unit housing.
I. Inspect intercoms, speaker systems,
radio-controlled, security devices or lawn
irrigation systems.
J. Offer guarantees or warranties.
K. Offer or perform any engineering services.
L. Offer or perform any trade or professional
service other than home inspection.
M. Research the history of the property, report
on its potential for alteration, modification,
extendibility, or its suitability for a specific
or proposed use for occupancy.
N. Determine the age of construction or
installation of any system structure, or
component of a building, or differentiate
between original construction or subsequent
additions, improvements, renovations or
replacements thereto.
O. Determine the insurability of a property.
|
4.
Glossary of Terms
4.1.
Accessible:
Can be approached or entered by the inspector
safely, without difficulty, fear or danger.
4.2.
Activate:
To turn on, supply power, or enable systems,
equipment, or devices to become active by normal
operating controls. Examples include turning on the
gas or water supply valves to the fixtures and
appliances and activating electrical breakers or
fuses.
4.3.
Adversely Affect:
Constitute, or potentially constitute, a negative or
destructive impact.
4.4.
Alarm System:
Warning devices, installed or free-standing,
including but not limited to: Carbon monoxide
detectors, flue gas and other spillage detectors,
security equipment, ejector pumps and smoke alarms.
4.5.
Appliance:
A household device operated by use of electricity or
gas. Not included in this definition are components
covered under central heating, central cooling or
plumbing.
4.6.
Architectural Service:
Any practice involving the art and science of
building design for construction of any structure or
grouping of structures and the use of space within
and surrounding the structures or the design, design
development, preparation of construction contract
documents, and administration of the construction
contract.
4.7.
Component:
A permanently installed or attached fixture, element
or part of a system.
4.8.
Condition:
The visible and conspicuous state of being of an
object.
4.9.
Crawlspace:
The area within the confines of the foundation and
between the ground and the underside of the lowest
floor structural component.
4.10.
Decorative:
Ornamental; not required for the operation of
essential systems and components of a home.
4.11.
Describe:
Report in writing a system or component by its type,
or other observed characteristics, to distinguish it
from other components used for the same purpose.
4.12.
Determine: To
arrive at an opinion or conclusion pursuant to
examination.
4.13.
Dismantle: To
open, take apart or remove any component, device or
piece that would not typically be opened, taken
apart or removed by an ordinary occupant.
4.14.
Engineering Service:
Any professional service or creative work requiring
engineering education, training, and experience and
the application of special knowledge of the
mathematical, physical and engineering sciences to
such professional service or creative work as
consultation, investigation, evaluation, planning,
design and supervision of construction for the
purpose of assuring compliance with the
specifications and design, in conjunction with
structures, buildings, machines, equipment, works or
processes.
4.15.
Enter: To
go into an area to observe all visible components.
4.16.
Evaluate:
To assess the systems, structures or components of a
dwelling.
4.17.
Examine:
To visually look. See Inspect.
4.18.
Foundation:
The base upon which the structure or wall rests;
usually masonry, concrete, or stone, and generally
partially underground.
4.19.
Function:
The action for which an item, component, or system
is specially fitted or used or for which an item,
component or system exists; to be in action or
perform a task.
4.20.
Functional:
Performing, or able to perform, a function.
4.21.
Home Inspection:
The process by which an inspector visually examines
the readily accessible systems and components of a
home and operates those systems and components
utilizing these Standards of Practice as a
guideline.
4.22.
Household Appliances:
Kitchen and laundry appliances, room air
conditioners, and similar appliances.
4.23.
Inspect:
To visually look at readily accessible systems and
components safely, using normal operating controls
and accessing readily accessible panels and areas.
4.24. Inspected Property: The readily
accessible areas of the buildings, site, items,
components, and systems included in the inspection.
4.25.
Inspector:
One who performs a real estate inspection.
4.26.
Installed:
Attached or connected such that the installed item
requires tool for removal.
4.27.
Material Defect:
Refer to section 1.2.
4.28.
Normal Operating Controls:
Devices such as thermostats that would be operated
by ordinary occupants which require no specialized
skill or knowledge.
4.29.
Observe:
To see through visually directed attention.
4.30.
Operate:
To cause systems to function or turn on with normal
operating controls.
4.31.
Readily Accessible:
An item or component is readily accessible if, in
the judgment of the inspector, it is capable of
being safely observed without movement of obstacles,
detachment or disengagement of connecting or
securing devices, or other unsafe or difficult
procedures to gain access.
4.32.
Recreational Facilities:
Spas, saunas, steam baths, swimming pools, tennis
courts, playground equipment, and other exercise,
entertainment or athletic facilities.
4.33.
Report:
A written communication (possibly including digital
images) of any material defects seen during the
inspection.
4.34.
Representative Number:
A sufficient number to serve as a typical or
characteristic example of the item(s) inspected.
4.35.
Safety Glazing:
Tempered glass, laminated glass, or rigid plastic.
4.36.
Shut Down: Turned
off, unplugged, inactive, not in service, not
operational, etc.
4.37.
Structural Component: A component which supports
non-variable forces or weights (dead loads) and
variable forces or weights (live loads).
4.38.
System:
An assembly of various components to function as a
whole.
4.39.
Technically Exhaustive:
A comprehensive and detailed examination beyond the
scope of a real estate home inspection which would
involve or include, but would not be limited to:
dismantling, specialized knowledge or training,
special equipment, measurements, calculations,
testing, research, analysis or other means.
4.40.
Unsafe:
A condition in a readily accessible, installed
system or component which is judged to be a
significant risk of personal injury during normal,
day-to-day use. The risk may be due to damage,
deterioration, improper installation or a change in
accepted residential construction standards.
4.41.
Verify:
To confirm or substantiate.
The
aforementioned terms are found within the SOP.
|
All content
copyright © 1999-2007
National Association of Certified Home Inspectors |
|
|
|
|
|
|