1. Definitions and Scope
|
1. Definitions and Scope
1.1. A Home inspection is a
non-invasive visual examination of a residential dwelling,
performed for a fee, which is designed to identify observed
material defects within specific components of said
dwelling. Components may include any combination of
mechanical, structural, electrical, plumbing, or other
essential systems or portions of the home, as identified and
agreed to by the Client and Inspector, prior to or during
the inspection process.
I. A home inspection is
intended to assist in evaluation of the overall condition
of the dwelling. The inspection is based on observation of
the visible and apparent condition of the structure and
its components on the date of the inspection and not the
determination of future conditions.
II. A home inspection will
not reveal every problem that exists or ever could exist,
but only those material defects observed on the day of the
inspection.
1.2. A Material defect is a
problem with a residential real property or any portion of
it that would have a significant adverse impact on the value
of the property or that involves an unreasonable risk to
people on the property. The fact that a structural element,
system or subsystem is near, at or beyond the end of the
normal useful life of such a structural element, system or
subsystem is not by itself a material defect.
1.3. An Inspection report
shall describe and identify in written format the inspected
systems, structures, and components of the dwelling and
shall identify material defects observed. Inspection reports
may contain recommendations regarding conditions reported or
recommendations for correction, monitoring or further
evaluation by professionals.
|
2. Standards of Practice
2.1. Roof
I. The inspector shall
inspect from ground level or eaves:
A. The roof covering.
B. The gutters.
C. The downspouts.
D. The vents, flashings, skylights, chimney and other
roof penetrations.
E. The general structure of the roof from the readily
accessible panels, doors or stairs.
II. The inspector is not
required to:
A. Walk on any roof
surface.
B. Predict the service life expectancy.
C. Inspect underground downspout diverter drainage
pipes.
D. Remove snow, ice, debris or other conditions that
prohibit the observation of the roof surfaces.
E. Inspect antennae, lightning arresters, or similar
attachments.
2.2. Exterior
I. The inspector shall
inspect:
A. The flashing and trim.
B. All exterior doors, decks, stoops, steps, stairs,
porches, railings, eaves, soffits, fascias, grading, and
walkways.
C. And report as in need of repair any spacings between
intermediate balusters, spindles, or rails for steps,
stairways, balconies, and railings that permit the
passage of an object greater than four inches in
diameter.
D. The vegetation, surface drainage and retaining walls
when these are likely to adversely affect the building.
E. And describe the exterior wall covering.
II. The inspector is not
required to:
A. Inspect or operate
screens, storm windows, shutters, awnings, fences,
outbuildings, or exterior accent lighting.
B. Inspect items, including window and door flashings,
which are not visible or readily accessible from the
ground.
C. Inspect geological, geotechnical, or hydrological
conditions.
D. Inspect recreational facilities.
E. Inspect seawalls, break-walls and docks.
F. Inspect erosion control and earth stabilization
measures.
G. Inspect for safety type glass.
H. Inspect underground utilities.
I. Inspect underground items.
J. Inspect wells or springs.
K. Inspect solar systems.
L. Inspect swimming pools or spas.
M. Inspect septic systems or cesspools.
N. Inspect playground equipment.
O. Inspect sprinkler systems.
P. Inspect drain fields or drywells.
Q. Determine the integrity of the thermal window seals
or damaged glass.
2.3. Basement, Foundation
& Crawlspace
I. The inspector shall
inspect:
A. The basement.
B. The foundation
C. The crawlspace.
D. The visible structural components.
E. Any present conditions or indications of active water
penetration by probing a representative sampling of
structural components where deterioration is believed to
be present or where clear indications of deterioration
are present.
F. And report any general indications of foundation
movement that are observed, such as but not limited to
sheetrock cracks, brick cracks, out-of-square door
frames or floor slopes.
II. The inspector is not
required to:
A. Enter any crawlspaces
that are not readily accessible or where entry could
cause damage or pose a hazard to the inspector in his or
her opinion.
B. Move stored items or debris.
C. Operate sump pumps with inaccessible floats.
D. Identify size, spacing, span, location or adequacy of
foundation bolting, bracing, joists or support systems.
E. Provide any engineering or architectural service.
F. Report on the adequacy of any structural system or
component.
2.4. Heating
I. The inspector shall
inspect:
A. The heating system and
describe the energy source and heating method using
normal operating controls.
B. And report as in need of repair electric furnaces
which do not operate.
C. And report if inspector deemed the furnace
inaccessible.
II. The
inspector is not required to:
A. Inspect or evaluate
interiors of flues or chimneys, fire chambers, the heat
exchanger, the humidifier or dehumidifier, the
electronic air filter, solar heating systems or fuel
tanks.
B. Inspect underground fuel tanks.
C. Determine the uniformity, temperature, flow, balance,
distribution, size, capacity, BTU, or supply adequacy of
the heating system.
D. Light pilot flames.
E. Activate heating, heat pump systems, or other heating
systems when ambient temperatures or other circumstances
are not conducive to safe operation or may damage the
equipment.
F. Operate electronic thermostats.
G. Evaluate fuel quality.
2.5. Cooling
I. The inspector shall
inspect:
A. The central cooling
equipment using normal operating controls.
II. The inspector is not
required to:
A. Determine the
uniformity, temperature, flow, balance, distribution,
size, capacity, BTU, or supply adequacy of the cooling
system.
B. Inspect window units, through-wall units, or
electronic air filters.
C. Operate equipment or systems if exterior temperature
is below 60 degrees Fahrenheit or when other
circumstances are not conducive to safe operation or may
damage the equipment.
D. Inspect or determine thermostat calibration, heat
anticipation or automatic setbacks or clocks.
E. Examine electrical current, coolant fluids or gasses,
or coolant leakage.
2.6. Plumbing
I. The inspector shall:
A. Inspect the main water
shut off valve.
B. Inspect the water heating equipment, including
combustion air, venting, connections, energy sources,
seismic bracing, and verify the presence or absence of
temperature-pressure relief valves and/or Watts 210
valves.
C. Flush toilets.
D. Run water in sinks, tubs, and showers.
E. Inspect the interior water supply including all
fixtures and faucets.
F. Inspect the drain, waste and vent systems,
including all fixtures.
G. Describe any visible fuel storage
systems.
H. Inspect the drainage sump pumps testing sumps with
accessible floats.
I. Inspect and describe the water supply, drain, waste
and main fuel shut-off valves, as well as the location
of the water main and main fuel shut-off valves.
J. Inspect and determine if the water supply is public
or private.
K. Inspect and report as in need of repair
deficiencies in the water supply by viewing the
functional flow in two fixtures operated
simultaneously.
L. Inspect and report as in need of repair
deficiencies in installation and identification of hot
and cold faucets.
M. Inspect and report as in need of repair mechanical
drain-stops that are missing or do not operate if
installed in sinks, lavatories and tubs.
N. Inspect and report as in need of repair commodes
that have cracks in the ceramic material, are
improperly mounted on the floor, leak, or have tank
components which do not operate.
II. The inspector is not
required to:
A. Light pilot flames.
B. Determine the size, temperature, age, life
expectancy or adequacy of the water heater.
C. Inspect interiors of flues or chimneys, water
softening or filtering systems, well pumps or tanks,
safety or shut-of valves, floor drains or sprinkler
systems.
D. Determine the exact flow rate, volume, pressure,
temperature, or adequacy of the water supply.
E. Determine the water quality or potability or the
reliability of the water supply or source.
F. Open closed plumbing access panels.
G. Inspect clothes washing machine connections.
H. Operate any main, branch or fixture valve except
fixture faucets and hose faucets attached to the
building.
I. Test shower pans, tub and shower surrounds or
enclosures for leakage.
J. Evaluate the compliance with local or state
conservation or energy standards, or the proper design
or sizing of any water, waste or venting components,
fixtures or piping.
K. Determine the effectiveness of anti-siphon,
back-flow prevention or drain-stop devices.
L. Determine whether there are sufficient clean-outs
for effective cleaning of drains.
M. Evaluate gas, liquid propane or oil storage tanks.
N. Excavate or otherwise uncover the private sewage
system or its components to determine size, adequacy
or efficiency.
O. Inspect water treatment systems or water filters.
P. Inspect pressure pumps or bladder tanks.
Q. Evaluate time to
obtain hot water at fixtures, or perform testing of
any kind to water heater elements.
R. Evaluate or determine
the adequacy of combustion air.
S. Test, operate, open
or close Watts 210 valves and/or TPR valves.
T. Examine ancillary
systems or components, such as, but not limited to,
those relating to solar water heating, hot water
circulation.
2.7. Electrical
I. The inspector shall
inspect:
A. The service line.
B. The meter box.
C. The main disconnect.
D. And determine the service amperage.
E. Panels, breakers and fuses.
F. The grounding.
G. The bonding.
H. A representative sampling of switches, receptacles,
light fixtures, and test all GFCI receptacles and GFCI
circuit breakers observed and deemed to be GFCI's
during the inspection.
I. And report the presence
of solid conductor aluminum branch circuit wiring if
readily visible.
J. And report on any GFCI-tested receptacles
in which power is not present, polarity is incorrect,
the receptacle is not grounded, is not
secured to the wall, the cover is not in place, the
ground fault circuit interrupter devices are not
properly installed or do not operate properly, or
evidence of arcing or excessive heat is present.
K. The service entrance conductors and the
condition of their sheathing.
L. The ground fault circuit interrupters with a GFCI
tester.
M. And describe the amperage rating of the service.
N. And report the absence of smoke detectors.
O. Service entrance cables and report as in need of
repair deficiencies in the integrity of the
insulation, drip loop, or separation of conductors at
weatherheads and clearances.
II. The inspector is not
required to:
A. Insert any tool, probe
or device into the main or sub-panels.
B. Operate electrical systems that are shut down.
C. Remove panel covers or dead front covers if not
readily accessible.
D. Operate over current protection devices.
E. Operate non-accessible smoke detectors.
F. Measure or determine the amperage or voltage of the
main service if not visibly labeled.
G. Inspect the alarm system and components.
H. Inspect the ancillary wiring.
I. Activate any electrical systems or branch circuits
which are not energized.
J. Operate overload devices.
K. Inspect low voltage systems, electrical de-icing
tapes, swimming pool wiring or any time-controlled
devices.
L. Verify the continuity of the connected service
ground.
M. Inspect private or emergency electrical supply
sources, including but not limited to generators,
windmills, photovoltaic solar collectors, or battery or
electrical storage facility.
N. Inspect spark or lightning arrestors.
O. Conduct drop voltage calculations.
P. Determine the accuracy of breaker labeling.
2.8. Fireplace
I. The inspector shall
inspect:
A. The fireplace, and
open and close the damper door if readily accessible and
operable.
B. Hearth extensions and other permanently installed
components.
C. And report as in need of repair deficiencies in the
lintel, hearth and material surrounding the fireplace,
including clearance from combustible materials
II. The inspector is not
required to:
A. Inspect the vent
system.
B. Inspect the interior of the chimney or flue, fire
doors or screens, seals or mantels.
C. Determine the need for a chimney sweep.
D. Operate gas fireplace inserts.
E. Light pilot flames.
F. Determine the appropriateness of such installation.
G. Inspect automatic fuel feed devices.
H. Inspect combustion make up devices.
I. Inspect heat distribution assists whether gravity
controlled or fan assisted.
J. Ignite or extinguish fires.
K. Determine draft characteristics.
L. Move fireplace inserts, stoves, or firebox contents.
M. Determine adequacy of draft, perform a smoke test or
dismantle or remove any component.
2.9. Attic, Ventilation &
Insulation
I. The inspector shall
inspect:
A. The insulation in
unfinished spaces.
B. The ventilation of attic spaces.
C. Mechanical ventilation systems.
D. And report on the general absence or lack of
insulation.
II. The inspector is not
required to:
A. Enter the attic or
unfinished spaces that are not readily accessible or
where entry could cause damage or pose a safety hazard
to the inspector in his or her opinion.
B. To move or touch insulation.
C. To move or touch vapor retarders.
D. Break or otherwise damage the surface finish or
weather seal on or around access panels and covers.
E. Identify the composition or the exact R-value of
insulation material.
F. Activate thermostatically operated fans.
G. Determine the types of materials used in
insulation/wrapping of pipes, ducts, jackets, boilers,
and wiring.
2.10. Doors, Windows &
Interior
I. The inspector shall:
A. Open and close a
representative number of doors and windows.
B. Inspect the walls, ceilings, steps, stairways, and
railings.
C. Inspect garage doors and garage door openers by
operating first by remote (if available) and
then by the installed automatic door control.
D. And report as in need of repair any installed
electronic sensors that are not operable or not
installed at proper heights above the garage door.
E. And report as in need of repair any door locks or
side ropes that have not been removed or disabled when
garage door opener is in use.
F. And report as in need of repair any windows that are
obviously fogged or display other evidence of broken
seals.
II. The inspector is not
required to:
A. Inspect paint,
wallpaper, window treatments or finish treatments.
B. Inspect central vacuum systems.
C. Inspect safety glazing in locations subject to human
impact.
D. Inspect security components.
E. Evaluate the fastening of countertops, cabinets, sink
tops and fixtures, or firewall compromises.
F. Move furniture, stored items, or any coverings like
carpets or rugs in order to inspect the concealed floor
structure.
G. Move drop ceiling tiles.
H. Inspect or move any household appliances.
I. Inspect or operate equipment housed in the garage
except as otherwise noted.
J. Verify or certify safe operation of any auto reverse
or related safety function of a garage door.
K. Operate or evaluate security bar release and opening
mechanisms, whether interior or exterior, including
compliance with local, state, or federal standards.
L. Operate any system, appliance or component that
requires the use of special keys, codes, combinations,
or devices.
M. Operate or evaluate self-cleaning oven cycles or
signal lights.
N. Determine leakage from microwave ovens.
O. Operate or examine any sauna, steam-jenny, kiln,
toaster, ice-maker, coffee-maker, can-opener,
bread-warmer, blender, instant hot water dispenser, or
other small, ancillary devices.
P. Inspect elevators.
Q. Inspect remote controls.
R. Inspect appliances.
S. Inspect items not permanently installed.
T. Examine or operate any above-ground, movable,
freestanding, or otherwise non-permanently installed
pool/spa or self-contained equipment.
U. Come into contact with any pool or spa water in order
to determine the system structure or components.
V. Determine the adequacy of spa jet water force or
bubble effect.
W. Determine the structural integrity or leakage of a
pool or spa.
3. Limitations, Exceptions
& Exclusions
3.1. Limitations:
I. An inspection is not
technically exhaustive.
II. An inspection will not identify concealed or latent
defects.
III. An inspection will not deal with aesthetic concerns
or what could be deemed matters of taste, cosmetic, etc.
IV. An inspection will not determine the suitability of
the property for any use.
V. An inspection does not determine the market value of
the property or its marketability.
VI. An inspection does not determine the advisability or
inadvisability of the purchase of the inspected property.
VII. An inspection does not determine the life expectancy
of the property or any components or systems therein.
VIII. An inspection does not include items not permanently
installed.
IX. These Standards of Practice apply only to homes with
four or fewer dwelling units.
3.2. Exclusions:
I. The inspectors are not
required to determine:
A. Property boundary
lines or encroachments.
B. The condition of any component or system that is not
readily accessible.
C. The service life expectancy of any component or
system.
D. The size, capacity, BTU, performance, or efficiency
of any component or system.
E. The cause or reason of any condition.
F. The cause for the need of repair or replacement of
any system or component.
G. Future conditions.
H. The compliance with codes or regulations.
I. The presence of evidence of rodents, animals or
insects.
J. The presence of mold, mildew or fungus.
K. The presence of air-borne hazards.
L. The presence of birds.
M. The presence of other flora or fauna.
N. The air quality.
O. The existence of asbestos.
P. The existence of environmental hazards.
Q. The existence of electro-magnetic fields.
R. The presence of hazardous materials including, but
not limited to, the presence of lead in paint.
S. Any hazardous waste conditions.
T. Any manufacturer recalls or conformance with
manufacturer installation or any information included in
the consumer protection bulletin.
U. Operating costs of systems.
V. Replacement or repair cost estimates.
W. The acoustical properties of any systems.
X. Estimates of how much it will cost to run any given
system.
II. The inspectors are not
required to operate:
A. Any system that is
shut down.
B. Any system that does not function properly.
C. Or evaluate low voltage electrical systems such as,
but not limited to:
1. Phone lines.
2. Cable lines.
3. Antennae.
4. Lights.
5. Remote controls.
D. Any system that does not turn on with the use of
normal operating controls.
E. Any shut off valve.
F. Any electrical disconnect or over current protection
devices.
G. Any alarm systems.
H. Moisture meters, gas detectors or similar equipment.
III. The inspectors are not
required to:
A. Move any personal
items or other obstructions, such as, but not limited
to:
1. Throw rugs.
2. Furniture.
3. Floor or wall coverings.
4. Ceiling tiles
5. Window coverings.
6. Equipment.
7. Plants.
8. Ice.
9. Debris.
10. Snow.
11. Water.
12. Dirt.
13. Foliage.
14. Pets
B. Dismantle, open, or
uncover any system or component.
C. Enter or access any area which may, in the opinion of
the inspector, to be unsafe or risk personal
safety.
D. Enter crawlspaces or other areas that are unsafe or
not readily accessible.
E. Inspect underground items such as, but not limited
to, underground storage tanks or other indications of
their presence, whether abandoned or actively used.
F. Do anything which, in the inspector's opinion, is
likely to be unsafe or dangerous to the inspector or
others or damage property, such as, but not limited to,
walking on roof surfaces, climbing ladders, entering
attic spaces or negotiating with dogs.
G. Inspect decorative items.
H. Inspect common elements or areas in multi-unit
housing.
I. Inspect intercoms, speaker systems, radio-controlled,
security devices or lawn irrigation systems.
J. Offer guarantees or warranties.
K. Offer or perform any engineering services.
L. Offer or perform any trade or professional service
other than home inspection.
M. Research the history of the property, report on its
potential for alteration, modification, extendibility,
or its suitability for a specific or proposed use for
occupancy.
N. Determine the age of construction or installation of
any system structure, or component of a building, or
differentiate between original construction or
subsequent additions, improvements, renovations or
replacements thereto.
O. Determine the insurability of a property.
|
4. Glossary of Terms
4.1. Accessible: Can be
approached or entered by the inspector safely, without
difficulty, fear or danger.
4.2. Activate: To turn on,
supply power, or enable systems, equipment, or devices to
become active by normal operating controls. Examples include
turning on the gas or water supply valves to the fixtures
and appliances and activating electrical breakers or fuses.
4.3. Adversely Affect:
Constitute, or potentially constitute, a negative or
destructive impact.
4.4. Alarm System: Warning
devices, installed or free-standing, including but not
limited to: Carbon monoxide detectors, flue gas and other
spillage detectors, security equipment, ejector pumps and
smoke alarms.
4.5. Appliance: A household
device operated by use of electricity or gas. Not included
in this definition are components covered under central
heating, central cooling or plumbing.
4.6. Architectural Service:
Any practice involving the art and science of building
design for construction of any structure or grouping of
structures and the use of space within and surrounding the
structures or the design, design development, preparation of
construction contract documents, and administration of the
construction contract.
4.7. Component: A permanently
installed or attached fixture, element or part of a system.
4.8. Condition: The visible
and conspicuous state of being of an object.
4.9. Crawlspace: The area
within the confines of the foundation and between the ground
and the underside of the lowest floor structural component.
4.10. Decorative: Ornamental;
not required for the operation of essential systems and
components of a home.
4.11. Describe: Report in
writing a system or component by its type, or other observed
characteristics, to distinguish it from other components
used for the same purpose.
4.12. Determine:
To arrive at
an opinion or conclusion pursuant to examination.
4.13. Dismantle:
To open,
take apart or remove any component, device or piece that
would not typically be opened, taken apart or removed by an
ordinary occupant.
4.14. Engineering Service:
Any professional service or creative work requiring
engineering education, training, and experience and the
application of special knowledge of the mathematical,
physical and engineering sciences to such professional
service or creative work as consultation, investigation,
evaluation, planning, design and supervision of construction
for the purpose of assuring compliance with the
specifications and design, in conjunction with structures,
buildings, machines, equipment, works or processes.
4.15. Enter: To go into an
area to observe all visible components.
4.16. Evaluate: To assess the
systems, structures or components of a dwelling.
4.17. Examine: To visually
look. See Inspect.
4.18. Foundation: The base
upon which the structure or wall rests; usually masonry,
concrete, or stone, and generally partially underground.
4.19. Function: The action
for which an item, component, or system is specially fitted
or used or for which an item, component or system exists; to
be in action or perform a task.
4.20. Functional: Performing,
or able to perform, a function.
4.21. Home Inspection: The
process by which an inspector visually examines the readily
accessible systems and components of a home and operates
those systems and components utilizing these Standards of
Practice as a guideline.
4.22. Household Appliances:
Kitchen and laundry appliances, room air conditioners, and
similar appliances.
4.23. Inspect: To visually
look at readily accessible systems and components safely,
using normal operating controls and accessing readily
accessible panels and areas.
4.24. Inspected Property: The readily accessible areas of
the buildings, site, items, components, and systems included
in the inspection.
4.25. Inspector: One who
performs a real estate inspection.
4.26. Installed: Attached or
connected such that the installed item requires tool for
removal.
4.27. Material Defect: Refer
to section 1.2.
4.28. Normal Operating
Controls: Devices such as thermostats that would be operated
by ordinary occupants which require no specialized skill or
knowledge.
4.29. Observe: To see through
visually directed attention.
4.30. Operate: To cause
systems to function or turn on with normal operating
controls.
4.31. Readily Accessible: An
item or component is readily accessible if, in the judgment
of the inspector, it is capable of being safely observed
without movement of obstacles, detachment or disengagement
of connecting or securing devices, or other unsafe or
difficult procedures to gain access.
4.32. Recreational
Facilities: Spas, saunas, steam baths, swimming pools,
tennis courts, playground equipment, and other exercise,
entertainment or athletic facilities.
4.33. Report: A written
communication (possibly including digital images) of any
material defects seen during the inspection.
4.34. Representative Number:
A sufficient number to serve as a typical or characteristic
example of the item(s) inspected.
4.35. Safety Glazing:
Tempered glass, laminated glass, or rigid plastic.
4.36. Shut Down: Turned off,
unplugged, inactive, not in service, not operational, etc.
4.37. Structural Component: A
component which supports non-variable forces or weights
(dead loads) and variable forces or weights (live loads).
4.38. System: An assembly of
various components to function as a whole.
4.39. Technically Exhaustive:
A comprehensive and detailed examination beyond the scope of
a real estate home inspection which would involve or
include, but would not be limited to: dismantling,
specialized knowledge or training, special equipment,
measurements, calculations, testing, research, analysis or
other means.
4.40. Unsafe: A condition in
a readily accessible, installed system or component which is
judged to be a significant risk of personal injury during
normal, day-to-day use. The risk may be due to damage,
deterioration, improper installation or a change in accepted
residential construction standards.
4.41. Verify: To confirm or
substantiate.
The aforementioned terms are
found within the SOP.
|
|
Visit
NACHI's full Glossary.
|
|
All content copyright © 1999-2007
National Association of Certified Home Inspectors
|
|